Chiller Module Specifications & Features
K-O Concepts Models LG-20/-60
K-O Concepts Inc. Chiller Part Number 2542-1730
LG-20 Cooling Capacity 2,000 watts (6,800 BTU's Typical Maximum)
  See Notes below for additional explanation.                              
LG-60 Cooling Capacity 6,000 watts (20,400 BTU's Typical Maximum)
  See Notes below for additional explanation.                              
Environment Indoor operation only with unrestricted ambient air required from
  5-30°C / 41-86°F.
Heat Dissipation To water (water-cooled)
  Note:  External cooling water supply required.
Process Water Standard Feature:  Demineralized (distilled water)
  Optional Feature:  Deionized (DI) water
Tank Capacity (Process Water) 4 quarts / 3.8 liters 
Temperature Range (Process Water) 50-30°C / 41-86°F
Temperature Controller (Process Water) Digital (PID) Controller:  Standard feature
Temperature Stability (Process Water)  
Note:  Temperature stability performance requires  
 a stable heat load. Digital controller stability w/ RTD sensor:  ±0.6°C (typical)
Heat Exchanger (Process Water)                                          Standard Feature:  Grade 316 stainless steel, copper brazed                                                                                       
Note:  Nickel brazed optional for DI water. Optional Feature:  Grade 316 stainless steel, nickel brazed
Standard Pumps (Process Water) Standard Feature:  PDM-3-10
  Optional Feature:  MD-70
Connections (Process Water) Standard:  ½ inch FPT
  Optional:  Quick disconnect fittings
Fill / Drain Feature (Process Water) Process water filled or drained with tools supplied via quick disconnect 
  fittings located on back panel.
Input Power Requirements 208/230 VAC, 1 Ø (standard)                             115 VAC, 1 Ø (optional)
Electrical Interface Signals Standard Feature:  Process water flow signal (reed switch).
Note:  All interface signals are contact closures Standard Feature:  Process water level signal (reed switch).
and are normally closed (N.C.) in a passed Standard Feature:  Process water temperature alarm (relay contact).
condition.  Interface signals accessed via  
(DA 15S) connector located on the back panel.  
Rack-Mount Configuration                                          Standard 19 inch rack-mount configuration allows for convenient
Note:  Cooling module cabinets are fully integration of cooling module with equipment to be cooled.  Enclosed 
 enclosed.  cabinet is equipped with handles for easy installation.
Dimensions (H x W x D) All Models:  11.72 x 17.19 x 17.22 inches (cabinet dimensions)
Note:  Front panel height equals 7 units. Front Panel Dimensions:  12.25H x 19.00W
Dry Weight  45 lbs / 20 kg
Optional Filter or Deionizer Cartridge Quick charge particle filter or deionizer cartridge located on back panel.
  Service elements with module installed into rack cabinet.
Optional Deionizer (DI) Water Monitor Provides contact closure signal to interface connector.  Alerts customer 
  when DI cartridge requires service.
Optional Rack Cabinet (H x W x D) All Models:  14.0 x 20.5 x 18.5 inches
Notes:
*     Maximum performance with process and supply water @ 4 GPM / 15 LPM in both loops.
*     Maximum cooling capacity ratings are with process water @ 20°C / 68°F and supply water @ 5°C / 41°F
*     Thermal performance chart available for cooling capacities @ other process temperatures.
*     Specifications are subject to change without notice.   
Page 3 of 4